February 12, 2020 in Our Experience
Goulburn Valley Health
A state-of-the-art redevelopment of Goulburn Valley Health in Shepparton will deliver new and expanded healthcare facilities to meet the growing commu...
September 16, 2016
Across all industries, Data Centre facilities large and small underpin the operation of business applications and processes. Maintaining reliable and continuous operation is critical. Disruptions due to fire events, whether damage is caused by the fire or the fire suppression systems, can cause very significant business interruption with substantial commercial effects.
This Advisory Note provides a brief guide to a design approach for providing fire protection systems in data processing facilities.
It must be noted that the minimum level of fire protection for a facility must meet Building Code requirements. These can be advised by the relevant Building Surveyor.
When looking at protecting a data facility from a disruption of service, the first step is to decide how critical the facility is to the continuity of your business. This will help determine the risk consequences and the level of fire protection investment required.
Sprinklers are one of the most reliable forms of fire protection. However, a wet system introduces the risk of water damage to equipment either by accidental discharge or collateral damage in a fire. Carefully designed concealed (or flush) type heads or guards can be considered to reduce the chance of accidental discharge due to mechanical damage to the sprinkler.
If the risk of water in the area is deemed too high, a dry pipe (or pre-action) system can be considered. This type of system has the sprinkler pipes in the critical area filled with compressed air or nitrogen. This type of ‘double interlock’ system only releases water when there is a smoke detection signal and an activated sprinkler head (via a drop in the air pressure in the pipework), that is the detection of both heat & smoke.
The introduction of a pre-action system (and most detection systems) requires a Fire Indicator Panel (FIP) to control the system. Either the main FIP or a local Sub-FIP may be used depending on the building. A Sub-FIP provides the benefit of local indication and control.
Smoke detection systems are typically either point type smoke detectors or aspirating type detection systems (e.g. VESDA®). Point type detectors provide a relatively low cost detection system but are limited in providing an escalating response. Aspirating systems can be configured with multiple outputs (up to 4) to provide a staged response to the fire. The lowest alarm level can be set to provide a very sensitive response for early occupant intervention.
If the risk of collateral water damage from a sprinkler system is deemed too high, a gas suppression system may be used either in conjunction with a sprinkler system as a first response system, or in lieu of a sprinkler system (subject to Building Surveyor approval). There are two main types of gas systems used; Inert gases or chemical agents. Both rely on a sealed enclosure to maintain design concentrations and a detection system to activate them. There are advantages and disadvantages with each of the different types of gases. Chemical agents tend to require a smaller storage footprint but some agents are detrimental to the environment. Inert gases require larger concentrations so pressure relief must be closely considered but can be used more readily to provide protection to multiple enclosures with variances in the protected volume.
The final step is to determine the control response to a fire and the interfaces to other systems. These interfaces may include local warning, paging, soft or hard power shutdown, mechanical shutdowns, and brigade call. This will usually depend on the level of proposed automation of the response. Some of these interfaces may be required to meet building codes. Care should be taken in determining the extent of the automation of the response as spurious alarms may result in accidental disruptions to the facility.
For further information, please contact us.
download pdfFebruary 12, 2020 in Our Experience
A state-of-the-art redevelopment of Goulburn Valley Health in Shepparton will deliver new and expanded healthcare facilities to meet the growing commu...
November 9, 2018 in News
Walker Fire Protection was recognised with both the 2018 Harry Marryatt Award for Fire Protection Company of the Year, 50+ employees and the award for...
August 7, 2018 in News
Featuring the historic Gatwick Hotel in St Kilda. Walker Fire Protection provided fire protection services for the project to Channel Nine.
June 20, 2018 in Advisory Notes
Computer performance continues to increase significantly as does the demand on cooling and power supply infrastructure. Data Centres have been identif...